VEGASWING 61

Vibrating level switch for liquids
Application area
The VEGASWING 61 universal level switch is used in liquids. It detects reliably and with a precision of up to a millimetre if a level is reached. It can be mounted in vessels and pipelines independent of the installation position. The instrument can be used as fully or empty alarm, as approved overfill protection, dry run protection or pump control.
Advantages
Setup without adjustment
Product-independent switching point
Very high reproducibility
Wear and maintenance-free
Function
The tuning fork is energized via the piezo drive to vibrate on its resonance frequency. The frequency of the fork reduces when being covered with medium. This frequency change is processed by the integrated electronics and converted into a switching command. To ensure a secure and reliable fastening of the piezo drive, an optimised screw connection is used.
|
Version